;------------------------------------------------------------------------------ ; This GSD (General Station Description) is provided by PI C3PG7 "PA Profile". ; This GSD is available for download at PI web server. ; The Profile GSDs cover the common subset of functions of devices of ; a specific PA device type providing interchangeability. ; ; This file describes the device type: ; Radar level transmitter ; with 2 Analog Inputs ; Physical layer RS-485. ; This file becomes valid with the PA profile version 4.0. ; ; Last modification: 2017-10-20 ;------------------------------------------------------------------------------ #Profibus_DP ;Standard definitions, valid for all device types with MBP GSD_Revision = 5 Vendor_Name = "Profile Process Control Devices" Revision = "PA 4.x" Protocol_Ident = 0 Station_Type = 0 FMS_supp = 0 Hardware_Release = "-" Software_Release = "-" 31.25_supp = 1 45.45_supp = 1 93.75_supp = 1 187.5_supp = 1 ;needed to support spec. network devices 500_supp = 1 ;needed to support spec. network devices 1.5M_supp = 1 ;needed to support spec. network devices 3M_supp = 1 ;needed to support spec. network devices 6M_supp = 1 ;needed to support spec. network devices 12M_supp = 1 ;needed to support spec. network devices MaxTsdr_31.25 = 100 MaxTsdr_45.45 = 250 ;exception for spec. network devices MaxTsdr_93.75 = 1000 MaxTsdr_187.5 = 60 MaxTsdr_500 = 100 MaxTsdr_1.5M = 150 MaxTsdr_3M = 250 MaxTsdr_6M = 450 MaxTsdr_12M = 800 Redundancy = 0 Repeater_Ctrl_Sig = 0 24V_Pins = 0 Freeze_Mode_supp = 0 Sync_Mode_supp = 0 Set_Slave_Add_supp = 1 Min_Slave_Intervall = 250 Modular_Station = 1 Slave_Family = 12@Profile4 ;end of standard definitions ;Device type specific definitions Model_Name = "Radar level (PhyL 1)" Ident_Number = 0xB321 Bitmap_Device = "PA_B321n" Max_Module = 2 Max_Input_Len = 10 ;2*AI(2*5) Max_Output_Len = 0 Max_Data_Len = 10 Max_Diag_Data_Len = 37 Modul_Offset = 1 Max_User_Prm_Data_Len = 22 Ext_User_Prm_Data_Const(0) = 0x80 ;DPV1 Status 1 Ext_User_Prm_Data_Const(1) = 0x00 ;DPV1 Status 2 Ext_User_Prm_Data_Const(2) = 0x08 ;DPV1 Status 3 ;--- Startup parameter of the Physical Block (Slot 0) PrmText = 1 ;STARTUP_PARAM_VALIDITY Text(0) = "Ignored" Text(1) = "Applied" EndPrmText ExtUserPrmData = 1 "Startup parameters" Unsigned8 0 0-1 Prm_Text_Ref = 1 EndExtUserPrmData Ext_User_Prm_Data_Const(3) = 5,66,0,0,0x00 Ext_User_Prm_Data_Ref(7) = 1 ;STARTUP_PARAM_VALIDITY (Unsigned8) ;--- Startup parameter of the transducer block - Radar level (Slot 1) PrmText = 2 ;Level units Text(1010) = "m" Text(1018) = "ft" EndPrmText ExtUserPrmData = 2 "Unit (Level, Distance)" Unsigned16 1010 0-65535 Prm_Text_Ref = 2 EndExtUserPrmData Ext_User_Prm_Data_Const(8) = 6,68,1,0,0x03,0xf2 Ext_User_Prm_Data_Ref(12) = 2 ;level unit (Unsigned16) Prm_Block_Structure_supp = 1 PrmCmd_supp = 1 ;slave supports PrmCmd Slave_Max_Switch_Over_Time = 20 ;=200 ms Slave_Redundancy_supp = 1 ;slave is not redundant but can be connected to a flying master Info_Text = "Radar level transmitter with PROFIBUS PA (MBP) communication \ interface." Ident_Maintenance_supp=1 ;----------- Description of extended DP features: --------------------- ; DPV1_Slave = 1 C1_Read_Write_supp = 1 C1_Max_Data_Len = 128 C1_Response_Timeout = 1000 C2_Read_Write_supp = 1 C2_Max_Data_Len = 128 C2_Max_Count_Channels = 1 Max_Initiate_PDU_Length = 52 C2_Response_Timeout = 1000 DPV1_Data_Types = 0 WD_Base_1ms_supp = 0 Check_Cfg_Mode = 0 ;----------- Description of device related diagnosis: --------------------- ; Unit_Diag_Bit(16) = "Status appears" Unit_Diag_Bit(17) = "Status disappears" Unit_Diag_Bit(35) = "Restart" ;DIA_WARMSTART Unit_Diag_Bit(36) = "Application reset" ;DIA_COLDSTART Unit_Diag_Bit(37) = "Maintenance required" ;DIA_MAINTENANCE Unit_Diag_Bit(40) = "Maintenance alarm" ;DIA_MAINTENANCE_ALARM Unit_Diag_Bit(41) = "Maintenance demanded" ;DIA_MAINTENANCE_DEMANDED Unit_Diag_Bit(42) = "Function check" ;DIA_FUNCTION_CHECK Unit_Diag_Bit(43) = "Out of specification" ;DIA_OUT_OF_SPEC Unit_Diag_Bit(44) = "Parameter update" ;DIA_UPDATE_EVENT Unit_Diag_Bit(55) = "Extension available" ;NE107_COMMON Unit_Diag_Bit(56) = "Sensor element exciter faulty" Unit_Diag_Bit_Help(56) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." Unit_Diag_Bit(57) = "Error in evaluation electronics" Unit_Diag_Bit_Help(57) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." Unit_Diag_Bit(58) = "Error in internal energy supply" Unit_Diag_Bit_Help(58) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." Unit_Diag_Bit(59) = "Error in sensor element" Unit_Diag_Bit_Help(59) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." Unit_Diag_Bit(60) = "Error in actuator element" Unit_Diag_Bit_Help(60) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." Unit_Diag_Bit(61) = "Faulty installat e.g. dead space" Unit_Diag_Bit_Help(61) = "Check installation." Unit_Diag_Bit(62) = "Parameter setting error" Unit_Diag_Bit_Help(62) = "Check parameter settings for consistency." Unit_Diag_Bit(63) = "Signal path broken or short cut" Unit_Diag_Bit_Help(63) = "Check signal path." Unit_Diag_Bit(64) = "Overloading" Unit_Diag_Bit_Help(64) = "Check load." Unit_Diag_Bit(65) = "Wrong polarity of aux power" Unit_Diag_Bit_Help(65) = "Check polarity." Unit_Diag_Bit(66) = "Maximum line length exceeded" Unit_Diag_Bit_Help(66) = "Check line length." Unit_Diag_Bit(67) = "Corrosion/abrasion by medium" Unit_Diag_Bit_Help(67) = "Replacement is recommended." Unit_Diag_Bit(68) = "Fouling on sensor element" Unit_Diag_Bit_Help(68) = "Cleaning is recommended." Unit_Diag_Bit(69) = "Auxil medium missing or insuffic" Unit_Diag_Bit_Help(69) = "Check auxiliary medium." Unit_Diag_Bit(70) = "Wear reserve used up (operation)" Unit_Diag_Bit_Help(70) = "Plan maintenance." Unit_Diag_Bit(71) = "Wear reserve used up (wear)" Unit_Diag_Bit_Help(71) = "Plan maintenance." Unit_Diag_Bit(72) = "Error in peripherals" Unit_Diag_Bit_Help(72) = "Check peripherals." Unit_Diag_Bit(73) = "Electromag interference too high" Unit_Diag_Bit_Help(73) = "Lower external electromagnetic interference." Unit_Diag_Bit(74) = "Temperature of medium too high" Unit_Diag_Bit_Help(74) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(75) = "Ambient temperature too high" Unit_Diag_Bit_Help(75) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(76) = "Vibration/Impact load too high" Unit_Diag_Bit_Help(76) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(77) = "Auxiliary power range off-spec" Unit_Diag_Bit_Help(77) = "Check power supply" Unit_Diag_Bit(78) = "Auxiliary medium missing" Unit_Diag_Bit_Help(78) = "Check auxiliary medium." Unit_Diag_Bit(79) = "Excessive temperature shock" Unit_Diag_Bit_Help(79) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(80) = "Deviation from measurement" Unit_Diag_Bit_Help(80) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." Unit_Diag_Bit(81) = "Humidity in electronics area" Unit_Diag_Bit_Help(81) = "Replacement is recommended." Unit_Diag_Bit(82) = "Medium in electronics area" Unit_Diag_Bit_Help(82) = "Replacement is recommended." Unit_Diag_Bit(83) = "Mechanical damage" Unit_Diag_Bit_Help(83) = "Replacement is recommended." Unit_Diag_Bit(84) = "Communication error" Unit_Diag_Bit_Help(84) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." Unit_Diag_Bit(85) = "Foreign material in electro area" Unit_Diag_Bit_Help(85) = "Replacement is recommended." ;NE107_RADAR (device specific) Unit_Diag_Bit(104) = "Change of running time, encrust?" Unit_Diag_Bit_Help(104) = "Remove encrustation." Unit_Diag_Bit(105) = "False echoes, encrustation?" Unit_Diag_Bit_Help(105) = "Remove encrustation." Unit_Diag_Bit(106) = "Wrong/no indication, foam" Unit_Diag_Bit_Help(106) = "Check process conditions." Unit_Diag_Bit(107) = "Poor reflection" Unit_Diag_Bit_Help(107) = "1. Check process conditions. 2. Check \ installation according to the installation instructions of the manufacturer." Unit_Diag_Bit(108) = "Problems with tank wall" Unit_Diag_Bit_Help(108) = "Check installation according to the installation \ instructions of the manufacturer." Unit_Diag_Bit(109) = "Surge tube or vent blocked" Unit_Diag_Bit_Help(109) = "Clean surge tube or venting." Unit_Diag_Bit(110) = "Nozzle too long/high" Unit_Diag_Bit_Help(110) = "Check installation according to the installation \ instructions of the manufacturer." Unit_Diag_Bit(111) = "No metallic reflecting surface" Unit_Diag_Bit_Help(111) = "Check installation according to the installation \ instructions of the manufacturer." Unit_Diag_Bit(112) = "Blocking distance underrun" Unit_Diag_Bit_Help(112) = "Check process conditions." Unit_Diag_Bit(113) = "Mechanical overloading of probe" Unit_Diag_Bit_Help(113) = "1. Check process conditions. 2. Check \ installation according to the installation instructions of the manufacturer." Unit_Diag_Bit(114) = "Probe lost or torn off" Unit_Diag_Bit_Help(114) = "Maintenance is required (check process \ conditions to avoid further defects)." Unit_Diag_Bit(115) = "Overload by external power" Unit_Diag_Bit_Help(115) = "Reduce external power." Unit_Diag_Bit(116) = "Product or moisture in coupler" Unit_Diag_Bit_Help(116) = "Replacement is recommended." Unit_Diag_Bit(117) = "Change of microwave speed" Unit_Diag_Bit_Help(117) = "1. Check process conditions. \ 2. Adapt configuration." Unit_Diag_Bit(118) = "Corr,abras, coating detachment" Unit_Diag_Bit_Help(118) = "Plan maintenance for cleaning/replacing." Unit_Diag_Bit(119) = "Probe in filling flow" Unit_Diag_Bit_Help(119) = "Check installation according to the installation \ instructions of the manufacturer." ;Unit_Diag_Bit(120) = "" ;Unit_Diag_Bit(121) = "" ;Unit_Diag_Bit(122) = "" ;Unit_Diag_Bit(123) = "" ;Unit_Diag_Bit(124) = "" ;Unit_Diag_Bit(125) = "" ;Unit_Diag_Bit(126) = "" ;Unit_Diag_Bit(127) = "" ;Unit_Diag_Bit(128) = "" ;Unit_Diag_Bit(129) = "" ;Unit_Diag_Bit(130) = "" ;Unit_Diag_Bit(131) = "" ;Unit_Diag_Bit(132) = "" ;Unit_Diag_Bit(133) = "" ;Unit_Diag_Bit(134) = "" ;Unit_Diag_Bit(135) = "" Unit_Diag_Bit(136) = "No clear interface Emulsion?" Unit_Diag_Bit_Help(136) = "Check process conditions." Unit_Diag_Bit(137) = "Wrong indication param setting" Unit_Diag_Bit_Help(137) = "Check device configuration." Unit_Diag_Bit(138) = "Diff dielecon too small" Unit_Diag_Bit_Help(138) = "Check process conditions." Unit_Diag_Bit(139) = "More than one interface" Unit_Diag_Bit_Help(139) = "Check process conditions." Unit_Diag_Bit(140) = "First phase thickness too small" Unit_Diag_Bit_Help(140) = "Check process conditions." ;Unit_Diag_Bit(141) = "" ;Unit_Diag_Bit(142) = "" ;Unit_Diag_Bit(143) = "" Unit_Diag_Bit(144) = "Attenuation due to deposits" Unit_Diag_Bit_Help(144) = "Remove deposits." Unit_Diag_Bit(145) = "False echoes due to deposits" Unit_Diag_Bit_Help(145) = "Remove deposits." Unit_Diag_Bit(146) = "Corrosion surge tube (inside)" Unit_Diag_Bit_Help(146) = "Replacement is recommended." Unit_Diag_Bit(147) = "Impurity in wave coupler area" Unit_Diag_Bit_Help(147) = "Replacement is recommended." Unit_Diag_Bit(148) = "Antenna immersed in product" Unit_Diag_Bit_Help(148) = "Increase distance between product and antenna." Unit_Diag_Bit(149) = "Wrong signal due to foam" Unit_Diag_Bit_Help(149) = "Check process conditions." Unit_Diag_Bit(150) = "Strong signal attenuation" Unit_Diag_Bit_Help(150) = "1. Check process conditions. 2. Check \ installation according to the installation instructions of the manufacturer." Unit_Diag_Bit(151) = "Shift of radar signal speed" Unit_Diag_Bit_Help(151) = "Check process conditions." Unit_Diag_Bit(152) = "Reflection" Unit_Diag_Bit_Help(152) = "Check process conditions." Unit_Diag_Bit(153) = "False interpretation of the echo" Unit_Diag_Bit_Help(153) = "Perform empty spectrum calibration." Unit_Diag_Bit(154) = "Bad polarization of the signal" Unit_Diag_Bit_Help(154) = "Check installation according to the installation \ instructions of the manufacturer." Unit_Diag_Bit(155) = "Surge tube or vent blocked" Unit_Diag_Bit_Help(155) = "Clean surge tube or venting." Unit_Diag_Bit(156) = "Nozzle too long for antenna" Unit_Diag_Bit_Help(156) = "Check installation according to the installation \ instructions of the manufacturer." Unit_Diag_Bit(157) = "Wall clearance, not vertical" Unit_Diag_Bit_Help(157) = "Check installation according to the installation \ instructions of the manufacturer." Unit_Diag_Bit(158) = "Corrosion on antenna" Unit_Diag_Bit_Help(158) = "Replacement is recommended." Unit_Diag_Bit(159) = "Attenuation due to fog or dust" Unit_Diag_Bit_Help(159) = "Check process conditions." Unit_Diag_Bit(160) = "Antenna signal blocked" Unit_Diag_Bit_Help(160) = "Check installation according to the installation \ instructions of the manufacturer." Unit_Diag_Bit(161) = "Blocking distance under-run" Unit_Diag_Bit_Help(161) = "Check process conditions." Unit_Diag_Bit(162) = "Echo too strong (overmodulation)" Unit_Diag_Bit_Help(162) = "Check installation according to the installation \ instructions of the manufacturer." ;--------------- UnitDiagType=254 X_Unit_Diag_Bit(35) = "Restart" ;DIA_WARMSTART X_Unit_Diag_Bit(36) = "Application reset" ;DIA_COLDSTART X_Unit_Diag_Bit(37) = "Maintenance required" ;DIA_MAINTENANCE X_Unit_Diag_Bit(40) = "Maintenance alarm" ;DIA_MAINTENANCE_ALARM X_Unit_Diag_Bit(41) = "Maintenance demanded" ;DIA_MAINTENANCE_DEMANDED X_Unit_Diag_Bit(42) = "Function check" ;DIA_FUNCTION_CHECK X_Unit_Diag_Bit(43) = "Out of specification" ;DIA_OUT_OF_SPEC X_Unit_Diag_Bit(44) = "Parameter update" ;DIA_UPDATE_EVENT X_Unit_Diag_Bit(55) = "Extension available" ;--- NE107_COMMON X_Unit_Diag_Bit(56) = "Sensor element exciter faulty" X_Unit_Diag_Bit_Help(56) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." X_Unit_Diag_Bit(57) = "Error in evaluation electronics" X_Unit_Diag_Bit_Help(57) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." X_Unit_Diag_Bit(58) = "Error in internal energy supply" X_Unit_Diag_Bit_Help(58) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." X_Unit_Diag_Bit(59) = "Error in sensor element" X_Unit_Diag_Bit_Help(59) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." X_Unit_Diag_Bit(60) = "Error in actuator element" X_Unit_Diag_Bit_Help(60) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." X_Unit_Diag_Bit(61) = "Faulty installat e.g. dead space" X_Unit_Diag_Bit_Help(61) = "Check installation." X_Unit_Diag_Bit(62) = "Parameter setting error" X_Unit_Diag_Bit_Help(62) = "Check parameter settings for consistency." X_Unit_Diag_Bit(63) = "Signal path broken or short cut" X_Unit_Diag_Bit_Help(63) = "Check signal path." X_Unit_Diag_Bit(64) = "Overloading" X_Unit_Diag_Bit_Help(64) = "Check load." X_Unit_Diag_Bit(65) = "Wrong polarity of aux power" X_Unit_Diag_Bit_Help(65) = "Check polarity." X_Unit_Diag_Bit(66) = "Maximum line length exceeded" X_Unit_Diag_Bit_Help(66) = "Check line length." X_Unit_Diag_Bit(67) = "Corrosion/abrasion by medium" X_Unit_Diag_Bit_Help(67) = "Replacement is recommended." X_Unit_Diag_Bit(68) = "Fouling on sensor element" X_Unit_Diag_Bit_Help(68) = "Cleaning is recommended." X_Unit_Diag_Bit(69) = "Auxil medium missing or insuffic" X_Unit_Diag_Bit_Help(69) = "Check auxiliary medium." X_Unit_Diag_Bit(70) = "Wear reserve used up (operation)" X_Unit_Diag_Bit_Help(70) = "Plan maintenance." X_Unit_Diag_Bit(71) = "Wear reserve used up (wear)" X_Unit_Diag_Bit_Help(71) = "Plan maintenance." X_Unit_Diag_Bit(72) = "Error in peripherals" X_Unit_Diag_Bit_Help(72) = "Check peripherals." X_Unit_Diag_Bit(73) = "Electromag interference too high" X_Unit_Diag_Bit_Help(73) = "Lower external electromagnetic interference." X_Unit_Diag_Bit(74) = "Temperature of medium too high" X_Unit_Diag_Bit_Help(74) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(75) = "Ambient temperature too high" X_Unit_Diag_Bit_Help(75) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(76) = "Vibration/Impact load too high" X_Unit_Diag_Bit_Help(76) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(77) = "Auxiliary power range off-spec" X_Unit_Diag_Bit_Help(77) = "Check power supply" X_Unit_Diag_Bit(78) = "Auxiliary medium missing" X_Unit_Diag_Bit_Help(78) = "Check auxiliary medium." X_Unit_Diag_Bit(79) = "Excessive temperature shock" X_Unit_Diag_Bit_Help(79) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(80) = "Deviation from measurement" X_Unit_Diag_Bit_Help(80) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." X_Unit_Diag_Bit(81) = "Humidity in electronics area" X_Unit_Diag_Bit_Help(81) = "Replacement is recommended." X_Unit_Diag_Bit(82) = "Medium in electronics area" X_Unit_Diag_Bit_Help(82) = "Replacement is recommended." X_Unit_Diag_Bit(83) = "Mechanical damage" X_Unit_Diag_Bit_Help(83) = "Replacement is recommended." X_Unit_Diag_Bit(84) = "Communication error" X_Unit_Diag_Bit_Help(84) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." X_Unit_Diag_Bit(85) = "Foreign material in electro area" X_Unit_Diag_Bit_Help(85) = "Replacement is recommended." ;NE107_RADAR (device specific) X_Unit_Diag_Bit(104) = "Change of running time, encrust?" X_Unit_Diag_Bit_Help(104) = "Remove encrustation." X_Unit_Diag_Bit(105) = "False echoes, encrustation?" X_Unit_Diag_Bit_Help(105) = "Remove encrustation." X_Unit_Diag_Bit(106) = "Wrong/no indication, foam" X_Unit_Diag_Bit_Help(106) = "Check process conditions." X_Unit_Diag_Bit(107) = "Poor reflection" X_Unit_Diag_Bit_Help(107) = "1. Check process conditions. 2. Check \ installation according to the installation instructions of the manufacturer." X_Unit_Diag_Bit(108) = "Problems with tank wall" X_Unit_Diag_Bit_Help(108) = "Check installation according to the installation \ instructions of the manufacturer." X_Unit_Diag_Bit(109) = "Surge tube or vent blocked" X_Unit_Diag_Bit_Help(109) = "Clean surge tube or venting." X_Unit_Diag_Bit(110) = "Nozzle too long/high" X_Unit_Diag_Bit_Help(110) = "Check installation according to the installation \ instructions of the manufacturer." X_Unit_Diag_Bit(111) = "No metallic reflecting surface" X_Unit_Diag_Bit_Help(111) = "Check installation according to the installation \ instructions of the manufacturer." X_Unit_Diag_Bit(112) = "Blocking distance underrun" X_Unit_Diag_Bit_Help(112) = "Check process conditions." X_Unit_Diag_Bit(113) = "Mechanical overloading of probe" X_Unit_Diag_Bit_Help(113) = "1. Check process conditions. 2. Check \ installation according to the installation instructions of the manufacturer." X_Unit_Diag_Bit(114) = "Probe lost or torn off" X_Unit_Diag_Bit_Help(114) = "Maintenance is required (check process \ conditions to avoid further defects)." X_Unit_Diag_Bit(115) = "Overload by external power" X_Unit_Diag_Bit_Help(115) = "Reduce external power." X_Unit_Diag_Bit(116) = "Product or moisture in coupler" X_Unit_Diag_Bit_Help(116) = "Replacement is recommended." X_Unit_Diag_Bit(117) = "Change of microwave speed" X_Unit_Diag_Bit_Help(117) = "1. Check process conditions. \ 2. Adapt configuration." X_Unit_Diag_Bit(118) = "Corr,abras, coating detachment" X_Unit_Diag_Bit_Help(118) = "Plan maintenance for cleaning/replacing." X_Unit_Diag_Bit(119) = "Probe in filling flow" X_Unit_Diag_Bit_Help(119) = "Check installation according to the installation \ instructions of the manufacturer." ;X_Unit_Diag_Bit(120) = "" ;X_Unit_Diag_Bit(121) = "" ;X_Unit_Diag_Bit(122) = "" ;X_Unit_Diag_Bit(123) = "" ;X_Unit_Diag_Bit(124) = "" ;X_Unit_Diag_Bit(125) = "" ;X_Unit_Diag_Bit(126) = "" ;X_Unit_Diag_Bit(127) = "" ;X_Unit_Diag_Bit(128) = "" ;X_Unit_Diag_Bit(129) = "" ;X_Unit_Diag_Bit(130) = "" ;X_Unit_Diag_Bit(131) = "" ;X_Unit_Diag_Bit(132) = "" ;X_Unit_Diag_Bit(133) = "" ;X_Unit_Diag_Bit(134) = "" ;X_Unit_Diag_Bit(135) = "" X_Unit_Diag_Bit(136) = "No clear interface Emulsion?" X_Unit_Diag_Bit_Help(136) = "Check process conditions." X_Unit_Diag_Bit(137) = "Wrong indication param setting" X_Unit_Diag_Bit_Help(137) = "Check device configuration." X_Unit_Diag_Bit(138) = "Diff dielecon too small" X_Unit_Diag_Bit_Help(138) = "Check process conditions." X_Unit_Diag_Bit(139) = "More than one interface" X_Unit_Diag_Bit_Help(139) = "Check process conditions." X_Unit_Diag_Bit(140) = "First phase thickness too small" X_Unit_Diag_Bit_Help(140) = "Check process conditions." ;X_Unit_Diag_Bit(141) = "" ;X_Unit_Diag_Bit(142) = "" ;X_Unit_Diag_Bit(143) = "" X_Unit_Diag_Bit(144) = "Attenuation due to deposits" X_Unit_Diag_Bit_Help(144) = "Remove deposits." X_Unit_Diag_Bit(145) = "False echoes due to deposits" X_Unit_Diag_Bit_Help(145) = "Remove deposits." X_Unit_Diag_Bit(146) = "Corrosion surge tube (inside)" X_Unit_Diag_Bit_Help(146) = "Replacement is recommended." X_Unit_Diag_Bit(147) = "Impurity in wave coupler area" X_Unit_Diag_Bit_Help(147) = "Replacement is recommended." X_Unit_Diag_Bit(148) = "Antenna immersed in product" X_Unit_Diag_Bit_Help(148) = "Increase distance between product and antenna." X_Unit_Diag_Bit(149) = "Wrong signal due to foam" X_Unit_Diag_Bit_Help(149) = "Check process conditions." X_Unit_Diag_Bit(150) = "Strong signal attenuation" X_Unit_Diag_Bit_Help(150) = "1. Check process conditions. 2. Check \ installation according to the installation instructions of the manufacturer." X_Unit_Diag_Bit(151) = "Shift of radar signal speed" X_Unit_Diag_Bit_Help(151) = "Check process conditions." X_Unit_Diag_Bit(152) = "Reflection" X_Unit_Diag_Bit_Help(152) = "Check process conditions." X_Unit_Diag_Bit(153) = "False interpretation of the echo" X_Unit_Diag_Bit_Help(153) = "Perform empty spectrum calibration." X_Unit_Diag_Bit(154) = "Bad polarization of the signal" X_Unit_Diag_Bit_Help(154) = "Check installation according to the installation \ instructions of the manufacturer." X_Unit_Diag_Bit(155) = "Surge tube or vent blocked" X_Unit_Diag_Bit_Help(155) = "Clean surge tube or venting." X_Unit_Diag_Bit(156) = "Nozzle too long for antenna" X_Unit_Diag_Bit_Help(156) = "Check installation according to the installation \ instructions of the manufacturer." X_Unit_Diag_Bit(157) = "Wall clearance, not vertical" X_Unit_Diag_Bit_Help(157) = "Check installation according to the installation \ instructions of the manufacturer." X_Unit_Diag_Bit(158) = "Corrosion on antenna" X_Unit_Diag_Bit_Help(158) = "Replacement is recommended." X_Unit_Diag_Bit(159) = "Attenuation due to fog or dust" X_Unit_Diag_Bit_Help(159) = "Check process conditions." X_Unit_Diag_Bit(160) = "Antenna signal blocked" X_Unit_Diag_Bit_Help(160) = "Check installation according to the installation \ instructions of the manufacturer." X_Unit_Diag_Bit(161) = "Blocking distance under-run" X_Unit_Diag_Bit_Help(161) = "Check process conditions." X_Unit_Diag_Bit(162) = "Echo too strong (overmodulation)" X_Unit_Diag_Bit_Help(162) = "Check installation according to the installation \ instructions of the manufacturer." EndUnitDiagType ;------------------------------------------------------------------------- ; ;max module text length-----------------" Module="Not in cyclic data transfer " 0x00 ;Empty module 0 Info_Text="No cyclic data selected for this slot. Function disabled" EndModule Module="Level" 0x42,0x84,0x08,0x05 1 EndModule Module="Distance" 0x42,0x84,0x08,0x05 2 EndModule ;----------- Description of the module assignment: --------------------- ; SlotDefinition Slot(1) = "" 1 1 Slot(2) = "" 2 0,2 EndSlotDefinition