;------------------------------------------------------------------------------ ; This GSD (General Station Description) is provided by PI C3PG7 "PA Profile". ; This GSD is available for download at PI web server. ; The Profile GSDs cover the common subset of functions of devices of ; a specific PA device type providing interchangeability. ; ; This file describes the device type: ; Pressure-type flow Transmitter ; with 2 Analog Input and 1 Totalizer ; Physical layer RS-485. ; This file becomes valid with the PA profile version 4.0. ; ; Last modification: 2019-12-05 ;------------------------------------------------------------------------------ #Profibus_DP ;Standard definitions, valid for all device types with RS-485 GSD_Revision = 5 Vendor_Name = "Profile Process Control Devices" Revision = "PA 4.x" Protocol_Ident = 0 Station_Type = 0 FMS_supp = 0 Hardware_Release = "-" Software_Release = "-" 9.6_supp = 1 19.2_supp = 1 45.45_supp = 1 93.75_supp = 1 187.5_supp = 1 ;needed to support spec. network devices 500_supp = 1 ;needed to support spec. network devices 1.5M_supp = 1 ;needed to support spec. network devices 3M_supp = 1 ;needed to support spec. network devices 6M_supp = 1 ;needed to support spec. network devices 12M_supp = 1 ;needed to support spec. network devices MaxTsdr_9.6 = 60 MaxTsdr_19.2 = 60 MaxTsdr_45.45 = 250 ;exception for spec. network devices MaxTsdr_93.75 = 60 MaxTsdr_187.5 = 60 MaxTsdr_500 = 100 MaxTsdr_1.5M = 150 MaxTsdr_3M = 250 MaxTsdr_6M = 450 MaxTsdr_12M = 800 Redundancy = 0 Repeater_Ctrl_Sig = 0 24V_Pins = 0 Freeze_Mode_supp = 0 Sync_Mode_supp = 0 Auto_Baud_supp = 1 Set_Slave_Add_supp = 1 Min_Slave_Intervall = 6 Modular_Station = 1 Slave_Family = 12@Profile4 ;end of standard definitions ;Device type specific definitions Model_Name = "Pressure-type flow (PhyL 0)" Ident_Number = 0xB312 Bitmap_Device = "PA_B312n" Max_Module = 4 Max_Input_Len = 15 ;2*AI + 1*TOT (3*5) Max_Output_Len = 1 ;SET_TOT Max_Data_Len = 16 Max_Diag_Data_Len = 35 Modul_Offset = 1 Max_User_Prm_Data_Len = 31 Ext_User_Prm_Data_Const(0) = 0x80 ;DPV1 Status 1 Ext_User_Prm_Data_Const(1) = 0x00 ;DPV1 Status 2 Ext_User_Prm_Data_Const(2) = 0x08 ;DPV1 Status 3 ;--- Startup parameter of the Physical Block (Slot 0) PrmText = 1 ;STARTUP_PARAM_VALIDITY Text(0) = "Ignored" Text(1) = "Applied" EndPrmText ExtUserPrmData = 1 "Startup parameters" Unsigned8 0 0-1 Prm_Text_Ref = 1 EndExtUserPrmData Ext_User_Prm_Data_Const(3) = 5,66,0,0,0x00 Ext_User_Prm_Data_Ref(7) = 1 ;STARTUP_PARAM_VALIDITY (Unsigned8) ;--- Startup parameter of the transducer block - Pressure (+ Level) + Flow (Slot 1) PrmText = 2 ;Pressure units Text(1133) = "kPa" Text(1130) = "Pa" Text(1137) = "bar" Text(1138) = "mbar" Text(1141) = "psi" Text(1155) = "inHg" EndPrmText ExtUserPrmData = 2 "Unit (Pressure)" Unsigned16 1133 0-65535 Prm_Text_Ref = 2 EndExtUserPrmData PrmText = 3 ;Volume flow units Text(1349) = "m3/h" Text(1351) = "L/s" Text(1357) = "ft3/min" Text(1363) = "gal/min" EndPrmText ExtUserPrmData = 3 "Unit (Volume flow)" Unsigned16 1349 0-65535 Prm_Text_Ref = 3 EndExtUserPrmData Ext_User_Prm_Data_Const(8) = 8,68,1,0,0x04,0x6d,0x04,035 Ext_User_Prm_Data_Ref(12) = 2 ;pressure unit (Unsigned16) Ext_User_Prm_Data_Ref(14) = 3 ;volume flow unit (Unsigned16) ;--- Startup parameters of the Volume Totalizer (Slot 4) PrmText = 4 Text(1034) = "m3" Text(1038) = "L" Text(1043) = "ft3" Text(1048) = "gal" EndPrmText ExtUserPrmData = 4 "Unit (Volume)" Unsigned16 1034 0-65535 Prm_Text_Ref = 4 EndExtUserPrmData Prm_Block_Structure_supp = 1 PrmCmd_supp = 1 ;slave supports PrmCmd Slave_Max_Switch_Over_Time = 20 ;=200 ms Slave_Redundancy_supp = 1 ;slave is not redundant but can be connected to a flying master Info_Text = "Pressure-type flow transmitter with PROFIBUS DP \ communication interface." Ident_Maintenance_supp = 1 ;----------- Description of extended DP features: --------------------- ; DPV1_Slave = 1 C1_Read_Write_supp = 1 C1_Max_Data_Len = 128 C1_Response_Timeout = 1000 C2_Read_Write_supp = 1 C2_Max_Data_Len = 128 C2_Max_Count_Channels = 1 Max_Initiate_PDU_Length = 52 C2_Response_Timeout = 1000 DPV1_Data_Types = 0 WD_Base_1ms_supp = 0 Check_Cfg_Mode = 0 ;----------- Description of device related diagnosis: --------------------- ; Unit_Diag_Bit(16) = "Status appears" Unit_Diag_Bit(17) = "Status disappears" Unit_Diag_Bit(35) = "Restart" ;DIA_WARMSTART Unit_Diag_Bit(36) = "Application reset" ;DIA_COLDSTART Unit_Diag_Bit(37) = "Maintenance required" ;DIA_MAINTENANCE Unit_Diag_Bit(40) = "Maintenance alarm" ;DIA_MAINTENANCE_ALARM Unit_Diag_Bit(41) = "Maintenance demanded" ;DIA_MAINTENANCE_DEMANDED Unit_Diag_Bit(42) = "Function check" ;DIA_FUNCTION_CHECK Unit_Diag_Bit(43) = "Out of specification" ;DIA_OUT_OF_SPEC Unit_Diag_Bit(44) = "Parameter update" ;DIA_UPDATE_EVENT Unit_Diag_Bit(55) = "Extension available" ;NE107_COMMON Unit_Diag_Bit(56) = "Sensor element exciter faulty" Unit_Diag_Bit_Help(56) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." Unit_Diag_Bit(57) = "Error in evaluation electronics" Unit_Diag_Bit_Help(57) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." Unit_Diag_Bit(58) = "Error in internal energy supply" Unit_Diag_Bit_Help(58) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." Unit_Diag_Bit(59) = "Error in sensor element" Unit_Diag_Bit_Help(59) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." Unit_Diag_Bit(60) = "Error in actuator element" Unit_Diag_Bit_Help(60) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." Unit_Diag_Bit(61) = "Faulty installat e.g. dead space" Unit_Diag_Bit_Help(61) = "Check installation." Unit_Diag_Bit(62) = "Parameter setting error" Unit_Diag_Bit_Help(62) = "Check parameter settings for consistency." Unit_Diag_Bit(63) = "Signal path broken or short cut" Unit_Diag_Bit_Help(63) = "Check signal path." Unit_Diag_Bit(64) = "Overloading" Unit_Diag_Bit_Help(64) = "Check load." Unit_Diag_Bit(65) = "Wrong polarity of aux power" Unit_Diag_Bit_Help(65) = "Check polarity." Unit_Diag_Bit(66) = "Maximum line length exceeded" Unit_Diag_Bit_Help(66) = "Check line length." Unit_Diag_Bit(67) = "Corrosion/abrasion by medium" Unit_Diag_Bit_Help(67) = "Replacement is recommended." Unit_Diag_Bit(68) = "Fouling on sensor element" Unit_Diag_Bit_Help(68) = "Cleaning is recommended." Unit_Diag_Bit(69) = "Auxil medium missing or insuffic" Unit_Diag_Bit_Help(69) = "Check auxiliary medium." Unit_Diag_Bit(70) = "Wear reserve used up (operation)" Unit_Diag_Bit_Help(70) = "Plan maintenance." Unit_Diag_Bit(71) = "Wear reserve used up (wear)" Unit_Diag_Bit_Help(71) = "Plan maintenance." Unit_Diag_Bit(72) = "Error in peripherals" Unit_Diag_Bit_Help(72) = "Check peripherals." Unit_Diag_Bit(73) = "Electromag interference too high" Unit_Diag_Bit_Help(73) = "Lower external electromagnetic interference." Unit_Diag_Bit(74) = "Temperature of medium too high" Unit_Diag_Bit_Help(74) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(75) = "Ambient temperature too high" Unit_Diag_Bit_Help(75) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(76) = "Vibration/Impact load too high" Unit_Diag_Bit_Help(76) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(77) = "Auxiliary power range off-spec" Unit_Diag_Bit_Help(77) = "Check power supply" Unit_Diag_Bit(78) = "Auxiliary medium missing" Unit_Diag_Bit_Help(78) = "Check auxiliary medium." Unit_Diag_Bit(79) = "Excessive temperature shock" Unit_Diag_Bit_Help(79) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(80) = "Deviation from measurement" Unit_Diag_Bit_Help(80) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." Unit_Diag_Bit(81) = "Humidity in electronics area" Unit_Diag_Bit_Help(81) = "Replacement is recommended." Unit_Diag_Bit(82) = "Medium in electronics area" Unit_Diag_Bit_Help(82) = "Replacement is recommended." Unit_Diag_Bit(83) = "Mechanical damage" Unit_Diag_Bit_Help(83) = "Replacement is recommended." Unit_Diag_Bit(84) = "Communication error" Unit_Diag_Bit_Help(84) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." Unit_Diag_Bit(85) = "Foreign material in electro area" Unit_Diag_Bit_Help(85) = "Replacement is recommended." ;NE107_PRESSURE(device specific) Unit_Diag_Bit(104) = "Pressure peaks outside range" Unit_Diag_Bit_Help(104) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(105) = "Deposits on the seal diaphragm" Unit_Diag_Bit_Help(105) = "Cleaning is recommended." Unit_Diag_Bit(106) = "Characteristic curve change" Unit_Diag_Bit_Help(106) = "Replacement is recommended." Unit_Diag_Bit(107) = "Inc. measuring err. (turn down)" Unit_Diag_Bit_Help(107) = "Check configuration." Unit_Diag_Bit(108) = "Wear on the seal diaphragm" Unit_Diag_Bit_Help(108) = "Replacement is recommended." Unit_Diag_Bit(109) = "Process seal at flush diaphragm" Unit_Diag_Bit_Help(109) = "Check flush diaphragm." Unit_Diag_Bit(110) = "Offset error due to inst. pos." Unit_Diag_Bit_Help(110) = "Check offset." Unit_Diag_Bit(111) = "Seal diaphragm deformation" Unit_Diag_Bit_Help(111) = "Replacement is recommended." Unit_Diag_Bit(112) = "Hydrogen penetration" Unit_Diag_Bit_Help(112) = "Replacement is recommended." Unit_Diag_Bit(113) = "Mean value deviation" Unit_Diag_Bit_Help(113) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(114) = "Pressure sensor system leakage" Unit_Diag_Bit_Help(114) = "Replacement is recommended." Unit_Diag_Bit(115) = "Hydrostatic offset" Unit_Diag_Bit_Help(115) = "Check offset." Unit_Diag_Bit(116) = "Gas seepage from pressure sensor" Unit_Diag_Bit_Help(116) = "Check pressure sensor." Unit_Diag_Bit(117) = "Add. measuring err. due to temp." Unit_Diag_Bit_Help(117) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(118) = "Delta T in capillary tubing" Unit_Diag_Bit_Help(118) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(119) = "Increase in compensation times" Unit_Diag_Bit_Help(119) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(120) = "Oleic acid leak" Unit_Diag_Bit_Help(120) = "Replacement is recommended." Unit_Diag_Bit(121) = "Pulse lines blocked" Unit_Diag_Bit_Help(121) = "Replacement is recommended." Unit_Diag_Bit(122) = "Gas inclusion in liquid medium" Unit_Diag_Bit_Help(122) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(123) = "Delta T in pulse lines" Unit_Diag_Bit_Help(123) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(124) = "Liquid inclusion in gas" Unit_Diag_Bit_Help(124) = "Check that the device is operated within its \ specifications." ;Unit_Diag_Bit(125) = "" ;Unit_Diag_Bit_Help(125) = "" ;Unit_Diag_Bit(126) = "" ;Unit_Diag_Bit_Help(126) = "" ;Unit_Diag_Bit(127) = "" ;Unit_Diag_Bit_Help(127) = "" Unit_Diag_Bit(128) = "Sedimentation on sensor" Unit_Diag_Bit_Help(128) = "Cleaning is recommended." Unit_Diag_Bit(129) = "Change of density" Unit_Diag_Bit_Help(129) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(130) = "Wrong height / wrong adjustment" Unit_Diag_Bit_Help(130) = "Check installation." Unit_Diag_Bit(131) = "Clogged membrane" Unit_Diag_Bit_Help(131) = "Cleaning is recommended. Replacement is \ recommended." Unit_Diag_Bit(132) = "Error with pulse line" Unit_Diag_Bit_Help(132) = "Replacement is recommended." Unit_Diag_Bit(133) = "Internal tank pressure influence" Unit_Diag_Bit_Help(133) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(134) = "Influence of temperature" Unit_Diag_Bit_Help(134) = "Check that the device is operated within its \ specifications." Unit_Diag_Bit(135) = "Hydrogen diffusion" Unit_Diag_Bit_Help(135) = "Replacement is recommended." Unit_Diag_Bit(136) = "Absence of bubble gas" Unit_Diag_Bit_Help(136) = "Check auxiliary medium." Unit_Diag_Bit(137) = "Air-bubble feed line blocked " Unit_Diag_Bit_Help(137) = "Replacement is recommended." Unit_Diag_Bit(138) = "Wear and tear of diaphragm" Unit_Diag_Bit_Help(138) = "Replacement is recommended." Unit_Diag_Bit(139) = "Gas seepage" Unit_Diag_Bit_Help(139) = "Replacement is recommended." Unit_Diag_Bit(140) = "Pressure rise at rel. of bubbles" Unit_Diag_Bit_Help(140) = "Check gas pressure." Unit_Diag_Bit(141) = "Pressure sensor overload" Unit_Diag_Bit_Help(141) = "Check gas pressure. Check feed line." Unit_Diag_Bit(142) = "Flow rate of bubble gas too high" Unit_Diag_Bit_Help(142) = "Check gas pressure." ;--------------- UnitDiagType=254 X_Unit_Diag_Bit(35) = "Restart" ;DIA_WARMSTART X_Unit_Diag_Bit(36) = "Application reset" ;DIA_COLDSTART X_Unit_Diag_Bit(37) = "Maintenance required" ;DIA_MAINTENANCE X_Unit_Diag_Bit(40) = "Maintenance alarm" ;DIA_MAINTENANCE_ALARM X_Unit_Diag_Bit(41) = "Maintenance demanded" ;DIA_MAINTENANCE_DEMANDED X_Unit_Diag_Bit(42) = "Function check" ;DIA_FUNCTION_CHECK X_Unit_Diag_Bit(43) = "Out of specification" ;DIA_OUT_OF_SPEC X_Unit_Diag_Bit(44) = "Parameter update" ;DIA_UPDATE_EVENT X_Unit_Diag_Bit(55) = "Extension available" ;--- NE107_COMMON X_Unit_Diag_Bit(56) = "Sensor element exciter faulty" X_Unit_Diag_Bit_Help(56) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." X_Unit_Diag_Bit(57) = "Error in evaluation electronics" X_Unit_Diag_Bit_Help(57) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." X_Unit_Diag_Bit(58) = "Error in internal energy supply" X_Unit_Diag_Bit_Help(58) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." X_Unit_Diag_Bit(59) = "Error in sensor element" X_Unit_Diag_Bit_Help(59) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." X_Unit_Diag_Bit(60) = "Error in actuator element" X_Unit_Diag_Bit_Help(60) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." X_Unit_Diag_Bit(61) = "Faulty installat e.g. dead space" X_Unit_Diag_Bit_Help(61) = "Check installation." X_Unit_Diag_Bit(62) = "Parameter setting error" X_Unit_Diag_Bit_Help(62) = "Check parameter settings for consistency." X_Unit_Diag_Bit(63) = "Signal path broken or short cut" X_Unit_Diag_Bit_Help(63) = "Check signal path." X_Unit_Diag_Bit(64) = "Overloading" X_Unit_Diag_Bit_Help(64) = "Check load." X_Unit_Diag_Bit(65) = "Wrong polarity of aux power" X_Unit_Diag_Bit_Help(65) = "Check polarity." X_Unit_Diag_Bit(66) = "Maximum line length exceeded" X_Unit_Diag_Bit_Help(66) = "Check line length." X_Unit_Diag_Bit(67) = "Corrosion/abrasion by medium" X_Unit_Diag_Bit_Help(67) = "Replacement is recommended." X_Unit_Diag_Bit(68) = "Fouling on sensor element" X_Unit_Diag_Bit_Help(68) = "Cleaning is recommended." X_Unit_Diag_Bit(69) = "Auxil medium missing or insuffic" X_Unit_Diag_Bit_Help(69) = "Check auxiliary medium." X_Unit_Diag_Bit(70) = "Wear reserve used up (operation)" X_Unit_Diag_Bit_Help(70) = "Plan maintenance." X_Unit_Diag_Bit(71) = "Wear reserve used up (wear)" X_Unit_Diag_Bit_Help(71) = "Plan maintenance." X_Unit_Diag_Bit(72) = "Error in peripherals" X_Unit_Diag_Bit_Help(72) = "Check peripherals." X_Unit_Diag_Bit(73) = "Electromag interference too high" X_Unit_Diag_Bit_Help(73) = "Lower external electromagnetic interference." X_Unit_Diag_Bit(74) = "Temperature of medium too high" X_Unit_Diag_Bit_Help(74) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(75) = "Ambient temperature too high" X_Unit_Diag_Bit_Help(75) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(76) = "Vibration/Impact load too high" X_Unit_Diag_Bit_Help(76) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(77) = "Auxiliary power range off-spec" X_Unit_Diag_Bit_Help(77) = "Check power supply" X_Unit_Diag_Bit(78) = "Auxiliary medium missing" X_Unit_Diag_Bit_Help(78) = "Check auxiliary medium." X_Unit_Diag_Bit(79) = "Excessive temperature shock" X_Unit_Diag_Bit_Help(79) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(80) = "Deviation from measurement" X_Unit_Diag_Bit_Help(80) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." X_Unit_Diag_Bit(81) = "Humidity in electronics area" X_Unit_Diag_Bit_Help(81) = "Replacement is recommended." X_Unit_Diag_Bit(82) = "Medium in electronics area" X_Unit_Diag_Bit_Help(82) = "Replacement is recommended." X_Unit_Diag_Bit(83) = "Mechanical damage" X_Unit_Diag_Bit_Help(83) = "Replacement is recommended." X_Unit_Diag_Bit(84) = "Communication error" X_Unit_Diag_Bit_Help(84) = "1. Restart device. 2. Check if failure recurs. \ 3. Replacement is recommended." X_Unit_Diag_Bit(85) = "Foreign material in electro area" X_Unit_Diag_Bit_Help(85) = "Replacement is recommended." ;NE107_PRESSURE(device specific) X_Unit_Diag_Bit(104) = "Pressure peaks outside range" X_Unit_Diag_Bit_Help(104) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(105) = "Deposits on the seal diaphragm" X_Unit_Diag_Bit_Help(105) = "Cleaning is recommended." X_Unit_Diag_Bit(106) = "Characteristic curve change" X_Unit_Diag_Bit_Help(106) = "Replacement is recommended." X_Unit_Diag_Bit(107) = "Inc. measuring err. (turn down)" X_Unit_Diag_Bit_Help(107) = "Check configuration." X_Unit_Diag_Bit(108) = "Wear on the seal diaphragm" X_Unit_Diag_Bit_Help(108) = "Replacement is recommended." X_Unit_Diag_Bit(109) = "Process seal at flush diaphragm" X_Unit_Diag_Bit_Help(109) = "Check flush diaphragm." X_Unit_Diag_Bit(110) = "Offset error due to inst. pos." X_Unit_Diag_Bit_Help(110) = "Check offset." X_Unit_Diag_Bit(111) = "Seal diaphragm deformation" X_Unit_Diag_Bit_Help(111) = "Replacement is recommended." X_Unit_Diag_Bit(112) = "Hydrogen penetration" X_Unit_Diag_Bit_Help(112) = "Replacement is recommended." X_Unit_Diag_Bit(113) = "Mean value deviation" X_Unit_Diag_Bit_Help(113) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(114) = "Pressure sensor system leakage" X_Unit_Diag_Bit_Help(114) = "Replacement is recommended." X_Unit_Diag_Bit(115) = "Hydrostatic offset" X_Unit_Diag_Bit_Help(115) = "Check offset." X_Unit_Diag_Bit(116) = "Gas seepage from pressure sensor" X_Unit_Diag_Bit_Help(116) = "Check pressure sensor." X_Unit_Diag_Bit(117) = "Add. measuring err. due to temp." X_Unit_Diag_Bit_Help(117) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(118) = "Delta T in capillary tubing" X_Unit_Diag_Bit_Help(118) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(119) = "Increase in compensation times" X_Unit_Diag_Bit_Help(119) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(120) = "Oleic acid leak" X_Unit_Diag_Bit_Help(120) = "Replacement is recommended." X_Unit_Diag_Bit(121) = "Pulse lines blocked" X_Unit_Diag_Bit_Help(121) = "Replacement is recommended." X_Unit_Diag_Bit(122) = "Gas inclusion in liquid medium" X_Unit_Diag_Bit_Help(122) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(123) = "Delta T in pulse lines" X_Unit_Diag_Bit_Help(123) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(124) = "Liquid inclusion in gas" X_Unit_Diag_Bit_Help(124) = "Check that the device is operated within its \ specifications." ;X_Unit_Diag_Bit(125) = "" ;X_Unit_Diag_Bit_Help(125) = "" ;X_Unit_Diag_Bit(126) = "" ;X_Unit_Diag_Bit_Help(126) = "" ;X_Unit_Diag_Bit(127) = "" ;X_Unit_Diag_Bit_Help(127) = "" X_Unit_Diag_Bit(128) = "Sedimentation on sensor" X_Unit_Diag_Bit_Help(128) = "Cleaning is recommended." X_Unit_Diag_Bit(129) = "Change of density" X_Unit_Diag_Bit_Help(129) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(130) = "Wrong height / wrong adjustment" X_Unit_Diag_Bit_Help(130) = "Check installation." X_Unit_Diag_Bit(131) = "Clogged membrane" X_Unit_Diag_Bit_Help(131) = "Cleaning is recommended. Replacement is \ recommended." X_Unit_Diag_Bit(132) = "Error with pulse line" X_Unit_Diag_Bit_Help(132) = "Replacement is recommended." X_Unit_Diag_Bit(133) = "Internal tank pressure influence" X_Unit_Diag_Bit_Help(133) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(134) = "Influence of temperature" X_Unit_Diag_Bit_Help(134) = "Check that the device is operated within its \ specifications." X_Unit_Diag_Bit(135) = "Hydrogen diffusion" X_Unit_Diag_Bit_Help(135) = "Replacement is recommended." X_Unit_Diag_Bit(136) = "Absence of bubble gas" X_Unit_Diag_Bit_Help(136) = "Check auxiliary medium." X_Unit_Diag_Bit(137) = "Air-bubble feed line blocked " X_Unit_Diag_Bit_Help(137) = "Replacement is recommended." X_Unit_Diag_Bit(138) = "Wear and tear of diaphragm" X_Unit_Diag_Bit_Help(138) = "Replacement is recommended." X_Unit_Diag_Bit(139) = "Gas seepage" X_Unit_Diag_Bit_Help(139) = "Replacement is recommended." X_Unit_Diag_Bit(140) = "Pressure rise at rel. of bubbles" X_Unit_Diag_Bit_Help(140) = "Check gas pressure." X_Unit_Diag_Bit(141) = "Pressure sensor overload" X_Unit_Diag_Bit_Help(141) = "Check gas pressure. Check feed line." X_Unit_Diag_Bit(142) = "Flow rate of bubble gas too high" X_Unit_Diag_Bit_Help(142) = "Check gas pressure." EndUnitDiagType ;------------------------------------------------------------------------- ; ;max module text length-----------------" Module="Not in cyclic data transfer " 0x00 ;Empty module 0 Info_Text="No cyclic data selected for this slot. Function disabled" EndModule Module="Pressure" 0x42,0x84,0x08,0x05 1 EndModule Module="Volume flow" 0x42,0x84,0x08,0x05 2 EndModule Module="Volume" 0x41,0x84,0x85 3 Ext_Module_Prm_Data_Len = 7 Ext_User_Prm_Data_Const(0) = 7,67,4,0,0x04,0x0A,1 Ext_User_Prm_Data_Ref(4) = 4 ;units (Unsigned16) ;INPUT_SELECTOR fixed to 1 (= volume flow) EndModule Module="Volume, Set" 0xC1,0x80,0x84,0x85 4 Ext_Module_Prm_Data_Len = 7 Ext_User_Prm_Data_Const(0) = 7,67,4,0,0x04,0x0A,1 Ext_User_Prm_Data_Ref(4) = 4 ;units (Unsigned16) ;INPUT_SELECTOR fixed to 1 (= volume flow) EndModule ;----------- Description of the module assignment: --------------------- ; SlotDefinition Slot(1) = "" 1 1 Slot(2) = "" 0 0 Slot(3) = "" 2 0,2 Slot(4) = "" 3 0,3,4 EndSlotDefinition